Will the BLUETTI PV100 FX Flexible Solar Panel work with the EcoFlow DELTA Pro 3?

Yes. One BLUETTI PV100 FX Flexible Solar Panel works with the EcoFlow DELTA Pro 3: about 45.3 V on a 20°F morning against the station's 150 V limit, and about 100 W in full sun. Two panels: works (1 panel on XT60 (High-PV) + 1 panel on XT60i (Low-PV)), about 200 W.

Verdict

Works

1 x PV100 FX Flexible Solar Panel into the DELTA Pro 3 (1 panel on XT60 (High-PV)) stays inside 30 to 150 V and under 15 A, even at 20F.

1 x PV100 FX Flexible Solar Panel1 panel on XT60 (High-PV)
DELTA Pro 3XT60 (High-PV)
Expected
100W
Voltage at 20F
45.3V
limit 150 V
Current
3.1A
cap 15 A
  • The two solar inputs are different. High-PV takes 30 to 150V, Low-PV takes 11 to 60V. A single small panel is too low for High-PV and will not charge there.
  • EcoFlow's manual: panel voltage rises in cold weather, so keep a margin below the limit when wiring in series.
  • For parallel wiring you need Y-branch (T-branch) solar cables.
  • 41.4 V open circuit is high for a 100 W panel: two in series reach 82.8 V, more than most stations take.
  • The BLUETTI US store sells it only in sets of 2 or more.
Cables to buy
  • Use an MC4 to XT60 solar cable.
BLUETTI PV100 FX Flexible Solar Panel

100 W, open-circuit 41.4 V, short-circuit 3.1 A. Brand page Panel details

EcoFlow DELTA Pro 3

Solar input XT60 (High-PV): 30 to 150 V; XT60i (Low-PV): 11 to 60 V, 2600 W max. Manual Station details

Change the count or temperature

Two panels: every way to wire them

WiringInputVolts at 20FAmpsWattsVerdict
1 panel on XT60 (High-PV) + 1 panel on XT60i (Low-PV)
Best option
XT60 (High-PV) + XT60i (Low-PV)45.33.1200Works
2 panels in parallel on XT60 (High-PV)
XT60 (High-PV)45.36.1200Works
2 panels in series on XT60 (High-PV)
XT60 (High-PV)90.73.1200Works
2 panels in parallel on XT60i (Low-PV)
XT60i (Low-PV)45.36.1200Works
2 panels in series on XT60i (Low-PV)
Open-circuit voltage 82.8V is above the station's 60V limit. Going over a station's input voltage limit can damage it.
XT60i (Low-PV)90.73.10Don't connect

Quick answers

Will the BLUETTI PV100 FX Flexible Solar Panel work with the EcoFlow DELTA Pro 3?

Yes. One BLUETTI PV100 FX Flexible Solar Panel works with the EcoFlow DELTA Pro 3: about 45.3 V on a 20°F morning against the station's 150 V limit, and about 100 W in full sun. Two panels: works (1 panel on XT60 (High-PV) + 1 panel on XT60i (Low-PV)), about 200 W.

Can I connect two PV100 FX Flexible Solar Panel panels to the DELTA Pro 3?

Yes, 1 panel on XT60 (High-PV) + 1 panel on XT60i (Low-PV). That gives about 200 W.

What cable do I need to connect the PV100 FX Flexible Solar Panel to the DELTA Pro 3?

Use an MC4 to XT60 solar cable.

Is it safe on a cold morning?

Panel voltage rises in the cold. One PV100 FX Flexible Solar Panel goes from 41.4 V on its label to about 45.3 V at 20°F and 46.7 V at 0°F. The DELTA Pro 3 accepts up to 150 V on the XT60 (High-PV).

Where to buy

$2,799 at the EcoFlow store, Oct 28, 2026
BuyAmazon

We may earn a commission if you buy through these links. It never changes a verdict.

Other panels that work with the DELTA Pro 3

→EcoFlow 400W Portable Solar Panel, about 800 W with two
→Anker SOLIX PS400 Bifacial, about 800 W with two
→BLUETTI PV350D, about 700 W with two
→Renogy 250W N-Type Bifacial Solar Panel, about 500 W with two
→EcoFlow NextGen 220W Bifacial Portable Solar Panel, about 438 W with two

All 33 panels checked against the DELTA Pro 3

Rules we applied
  • EcoFlow DELTA Pro 3: solar input 30 to 150 V on the Solar in 1 (XT60 (High-PV)). EcoFlow sets this limit on open-circuit voltage (Voc), so we hold the panels' Voc on your coldest morning to it.
  • Cold raises panel voltage: we add 0.30% per °C below 77F (25°C), a typical figure, since this panel does not publish its own. At 20F one panel's 41.4 V becomes 45.3 V.
  • Current over the 15 A cap is safe: the station takes 15 A and you get fewer watts. We count only the capped watts.
  • Max 1,600 W on this input, 2,600 W across all inputs.
Assumptions
  • Cold-morning voltage uses 0.30% per °C, typical for crystalline panels. This panel's own value is not published.
  • Expected watts are the best case in full sun. Real-world midday output is usually 60 to 80% of that.