Will the Anker SOLIX PS200 Bifacial work with the EcoFlow DELTA 3 Ultra Plus?
Yes, with a catch. Fine in mild weather (57.6V), but on a 20°F (-7°C) morning the open-circuit voltage rises to about 63.1V, above the 60V limit. Cold makes panels push more voltage. Two panels: works, with a catch (1 panel on Solar input 1 (XT60i) + 1 panel on Solar input 2 (XT60i)), about 400 W.
Works, with a catch
It charges, but read the note. Best option: 1 panel on Solar input 1 (XT60i).
- Fine in mild weather (57.6V), but on a 20°F (-7°C) morning the open-circuit voltage rises to about 63.1V, above the 60V limit. Cold makes panels push more voltage.
- The panel's plug type is not confirmed yet. Check the label or the box before buying a cable.
200 W, open-circuit 57.6 V, short-circuit 4.4 A, working 48 V / 4.2 A. Unconfirmed Panel details
EcoFlow DELTA 3 Ultra PlusSolar input Solar input 1 (XT60i): 11 to 60 V; Solar input 2 (XT60i): 11 to 60 V, 1600 W max. Manual Station details
Change the count or temperatureTwo panels: every way to wire them
| Wiring | Input | Volts at 20F | Amps | Watts | Verdict |
|---|---|---|---|---|---|
| 1 panel on Solar input 1 (XT60i) + 1 panel on Solar input 2 (XT60i) Fine in mild weather (57.6V), but on a 20°F (-7°C) morning the open-circuit voltage rises to about 63.1V, above the 60V limit. Cold makes panels push more voltage. | Solar input 1 (XT60i) + Solar input 2 (XT60i) | 63.1 | 4.2 | 400 | Works, with a catch |
| 2 panels in parallel on Solar input 1 (XT60i) Fine in mild weather (57.6V), but on a 20°F (-7°C) morning the open-circuit voltage rises to about 63.1V, above the 60V limit. Cold makes panels push more voltage. | Solar input 1 (XT60i) | 63.1 | 8.3 | 399 | Works, with a catch |
| 2 panels in parallel on Solar input 2 (XT60i) Fine in mild weather (57.6V), but on a 20°F (-7°C) morning the open-circuit voltage rises to about 63.1V, above the 60V limit. Cold makes panels push more voltage. | Solar input 2 (XT60i) | 63.1 | 8.3 | 399 | Works, with a catch |
| 2 panels in series on Solar input 1 (XT60i) Open-circuit voltage 115.2V is above the station's 60V limit. Going over a station's input voltage limit can damage it. | Solar input 1 (XT60i) | 126.1 | 4.2 | 0 | Don't connect |
| 2 panels in series on Solar input 2 (XT60i) Open-circuit voltage 115.2V is above the station's 60V limit. Going over a station's input voltage limit can damage it. | Solar input 2 (XT60i) | 126.1 | 4.2 | 0 | Don't connect |
Quick answers
Will the Anker SOLIX PS200 Bifacial work with the EcoFlow DELTA 3 Ultra Plus?
Yes, with a catch. Fine in mild weather (57.6V), but on a 20°F (-7°C) morning the open-circuit voltage rises to about 63.1V, above the 60V limit. Cold makes panels push more voltage. Two panels: works, with a catch (1 panel on Solar input 1 (XT60i) + 1 panel on Solar input 2 (XT60i)), about 400 W.
Can I connect two PS200 Bifacial panels to the DELTA 3 Ultra Plus?
Yes, 1 panel on Solar input 1 (XT60i) + 1 panel on Solar input 2 (XT60i). That gives about 400 W, with one catch: Fine in mild weather (57.6V), but on a 20°F (-7°C) morning the open-circuit voltage rises to about 63.1V, above the 60V limit. Cold makes panels push more voltage..
What cable do I need to connect the PS200 Bifacial to the DELTA 3 Ultra Plus?
The panel's plug type is not confirmed yet. Check the label or the box before buying a cable.
Is it safe on a cold morning?
Panel voltage rises in the cold. One PS200 Bifacial goes from 57.6 V on its label to about 63.1 V at 20°F and 65 V at 0°F. The DELTA 3 Ultra Plus accepts up to 60 V on the Solar input 1 (XT60i).
Where to buy
We may earn a commission if you buy through these links. It never changes a verdict.
Other panels that work with the DELTA 3 Ultra Plus
- EcoFlow DELTA 3 Ultra Plus: solar input 11 to 60 V on the Solar in 1 (Solar input 1 (XT60i)). EcoFlow sets this limit on open-circuit voltage (Voc), so we hold the panels' Voc on your coldest morning to it.
- Cold raises panel voltage: we add 0.30% per °C below 77F (25°C), a typical figure, since this panel does not publish its own. At 20F one panel's 57.6 V becomes 63.1 V.
- Current over the 18 A cap is safe: the station takes 18 A and you get fewer watts. We count only the capped watts.
- Max 800 W on this input, 1,600 W across all inputs.
- Cold-morning voltage uses 0.30% per °C, typical for crystalline panels. This panel's own value is not published.
- Expected watts are the best case in full sun. Real-world midday output is usually 60 to 80% of that.
- Some numbers for Anker SOLIX PS200 Bifacial come from a shop listing we have not confirmed in the manual yet.