Will the Rich Solar MEGA 200 PRO FLEX (24V) work with the Anker SOLIX S2000?
Yes. One Rich Solar MEGA 200 PRO FLEX (24V) works with the Anker SOLIX S2000: about 44.7 V on a 20°F morning against the station's 60 V limit, and about 200 W in full sun. Two panels: works (2 panels in parallel on XT60i), about 400 W.
Works
1 x MEGA 200 PRO FLEX (24V) into the S2000 (1 panel on XT60i) stays inside 11 to 60 V and under 12.5 A, even at 20F.
- The brand does not say whether its voltage limit is open-circuit or working voltage, so we check against the stricter open-circuit number.
- A 24 V panel: 40.8 V open circuit on its own, so two in series only suit high-voltage solar inputs.
- Use an MC4 to XT60i solar cable.
200 W, open-circuit 40.8 V, short-circuit 6.2 A, working 34.2 V / 5.9 A. Brand page Panel details
Anker SOLIX S2000Solar input XT60i: 11 to 60 V, 400 W max. Manual Station details
Change the count or temperatureTwo panels: every way to wire them
| Wiring | Input | Volts at 20F | Amps | Watts | Verdict |
|---|---|---|---|---|---|
| 2 panels in parallel on XT60i The brand does not say whether its voltage limit is open-circuit or working voltage, so we check against the stricter open-circuit number. | XT60i | 44.7 | 11.7 | 400 | Works |
| 2 panels in series on XT60i Open-circuit voltage 81.6V is above the station's 60V limit. Going over a station's input voltage limit can damage it. | XT60i | 89.4 | 5.9 | 0 | Don't connect |
Quick answers
Will the Rich Solar MEGA 200 PRO FLEX (24V) work with the Anker SOLIX S2000?
Yes. One Rich Solar MEGA 200 PRO FLEX (24V) works with the Anker SOLIX S2000: about 44.7 V on a 20°F morning against the station's 60 V limit, and about 200 W in full sun. Two panels: works (2 panels in parallel on XT60i), about 400 W.
Can I connect two MEGA 200 PRO FLEX (24V) panels to the S2000?
Yes, 2 panels in parallel on XT60i. That gives about 400 W.
What cable do I need to connect the MEGA 200 PRO FLEX (24V) to the S2000?
Use an MC4 to XT60i solar cable.
Is it safe on a cold morning?
Panel voltage rises in the cold. One MEGA 200 PRO FLEX (24V) goes from 40.8 V on its label to about 44.7 V at 20°F and 46 V at 0°F. The S2000 accepts up to 60 V on the XT60i.
Where to buy
We may earn a commission if you buy through these links. It never changes a verdict.
Other panels that work with the S2000
- Anker SOLIX S2000: solar input 11 to 60 V on the Solar in (XT60i). Anker SOLIX does not say whether this limit is open-circuit or working voltage, so we use the stricter reading: open-circuit voltage on your coldest morning.
- Cold raises panel voltage: we add 0.30% per °C below 77F (25°C), a typical figure, since this panel does not publish its own. At 20F one panel's 40.8 V becomes 44.7 V.
- Current over the 12.5 A cap is safe: the station takes 12.5 A and you get fewer watts. We count only the capped watts.
- Max 400 W on this input.
- Cold-morning voltage uses 0.30% per °C, typical for crystalline panels. This panel's own value is not published.
- Expected watts are the best case in full sun. Real-world midday output is usually 60 to 80% of that.